Trouble shooting
DMC810GL Installation Manual Rev E.docx 8
Check the following list. If you are still unable to rectify the situation, contact your nearest Dynalite office. A complete list of
distributors worldwide can be found on the Internet at: www.philips.com/dynalite
Please ensure that you have completed the following prior to calling our technical support department.
Check all symptoms in the Troubleshooting list
Check for any deviations between the installation and the installation instructions
Make a list of the model numbers of all devices used in the system
Dimmer does not operate at all. No Service LED
activity. Power supply indicator LED on PCB not lit.
Incorrect connection of mains supply, or no
power available.
Check power supply to dimmer. Check Line and
Neutral input connections.
Power supply indicator LED lit, but no Service LED
activity.
Supply voltage too low, short circuit on
network. Control PCB faulty.
Check supply voltage is at least 75% of rated
voltage. Check 12V terminal voltages.
Disconnect network bus and restore power.
Replace control PCB.
Dimmer will not respond to control panel push
buttons.
Control panel incorrectly wired or incorrect
configuration.
Check operation of LEDs on control panel. Push
button on panel and study response of service
LED.
Dimmer operates properly but circuit breakers keep
tripping.
Instant tripping: - short circuit on load.
Delayed tripping: - dimmer overloaded.
Check load wiring for short circuits. Verify
dimmer loading with current tester (don‟t forget to
de-rate for low power-factor loads and
transformer losses). Check that the breaker
terminals are tight.
Fluorescent lights won‟t dim.
Wrong type of ballast or ballast incorrectly
wired.
Check ballast type. Check actual wiring against
ballast manufacturer‟s diagram. Check 1-
10V/DSI, DALI Broadcast settings.
specification
230V ±14% 50/60Hz Single Phase at 40A
4 x 10A dimmed (leading edge phase control) outputs
4 x 10A switched outputs
4 x HF ballast control outputs selectable to DALI Broadcast, 1-10V DC, DSI
4 x 10A 6kA single pole thermal magnetic circuit breakers
Triac 600V, 40A nom. 400A surge
Relay 16A nom. (resistive), Fluorescent 800A surge, Incandescent 165A surge,
Regulated outputs
Over voltage protection
Surge protection
Brownout/Sag protection
Spike protection
Soft Start
Interference Suppression:
Iron powder toroidal choke
1 x RS485 DyNet/DMX512 serial port
1 x programmable dry contact AUX input
Service Switch
Diagnostic LED
Programmable Logic Controller
Dynalite Accessory Module enabled
200mA (supply for approx 10 panels)
Line, Neutral – 2 x 10mm
2
max conductor size
Line, Neutral for each channels 1-8
2 x 4mm
2
max conductor size
Earth link bar provided
0V/DSI/DALI, +V/DSI/DALI for channels 9-12
1 x 2.5mm
2
max conductor size
Mains – 8 x 25mm dia. knockout
Data – 1 x 25mm dia. knockout
Diagnostic Functions:
(DTK600, DLight or BAS interface required
for displaying and analysing diagnostic data)
Device Online/Offline status
Circuit breaker trip reporting (optional)
Circuit run time tracking
0 - 40C ambient temperature, 0% to 95% RH non condensing.
Alloy/Steel wall mount case with epoxy finish
Height 370mm x Width 215mm x Depth 170mm (excludes wall brackets)
DMC810GL Installation Manual Rev E.doc Specifications and design subject to change without notice.
Dynalite Manufactured by WMGD Pty Ltd (ABN 33 097 246 921). All rights reserved. Dynalite, Dimtek, DyNet and DLight and associated logos are the registered
trademarks of Dynalite Intelligent Light Pty Ltd. Not to be reproduced without permission.
Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-mail: dynalite.info@philips.com Web: Philips.com/dynalite
Comments to this Manuals